- Imported Honeywell PT1000 temperature sensor for more precise temperature control
- Fixed value and program control
- With automatic start, automatic stop, timed operation, clock display function
- Ambient temperature detection function
- with temperature calibration
Door switch monitoring function
- Five-level automatic defrost function and manual defrost function
- Logging function (touch screen implementation)
- Fault monitoring, alarm, recording function (touch screen implementation)
- Level 4 password function: login password, operator password, administrator password
(touch screen implementation)
- Three power-off mode selection functions: power failure recovery, stop or restart,Senior administrator password (touch screen implementation)
- Curve display function Touch screen implementation
-GPRS SMS alarm function Touch screen implementation
- Real-time data and historical data printing functions
- touch screen data storage function; touch screen implementation
- Ambient temperature detection function
- Optional computer monitoring software for connecting 6 devices
- with temperature calibration
- Water level monitoring and automatic water replenishment function (controlled humidity type)
Effective volume | LCD uncontrolled humidity series | Touch screen uncontrolled wet series | LCD moisture control series | Touch screen control wet series |
150L | MI-150 | MI-150T | HlI150 | HMI150T |
250L | MI-250 | MI-250T | HlI250 | HMI250T |
450L | MI-450 | MI-450T | HII450 | HMI450T |
750L | MI-750 | MI-750T | HII750 | HMI750T |
1100L | MI1100 | MI1100T | HMI1100 | HMI1100T |
Effective volume | 150 | 250 | 450 | 750 |
Control precision | ±0.1℃ | ±0.1℃ | ±0.1℃ | ±0.1℃ |
Temperature range |
0℃~70℃ | 0℃~70℃ | 0℃~70℃ | 0℃~70℃ |
Temperature display accuracy | 0.1℃ | 0.1℃ | 0.1℃ | 0.℃ |
Humidity range | No | No | 30~95% | 30~95% |
Humidity fluctuation | No | No | ±5%rh | ±5%rh |
Curve display function | No | Have | No | Have |
Data monitoring function | No | Have | No | Have |
Level 4 password function | No | Have |
No | Have |
Data storage function | No | Have | No | Have |
Fault monitoring, alarm, recording | No | Have | No | Have |
Temperature control method | Fuzzy intelligenceP.I.D | Fuzzy intelligenceP.I.D | Fuzzy intelligenceP.I.D | Fuzzy intelligenceP.I.D |
Program control | Puddy mode and program mode | |||
Defrosting method | Level 5 automatic defrost and manual defrost | |||
Frost-free area | No frost running above 20 degrees Celsius, no fluctuation in temperature | |||
Temperature Sensor | Import Honeywell PT1000 | |||
Three power-down mode selection functions | Power failure recovery, stop or restart | |||
Test hole | Left and right double test holes | |||
Insulation Materials | Polyurethane foam | |||
power supply | AC 220V±10%50HZ/60HZ |
Volume (liter) | 150 | 250 | 450 | 750 | 1100 |
Temperature uniformity (at 37 ° C时) | ±0.5℃ | ±0.5℃ | ±0.5℃ | ±0.8℃ | ±0.8℃ |
Heating power | 500W | 750W | 800W |
1000W | 1000W |
Cooling power | 1100W | 1500W | 2000W | 2500W | 3000W |
Liner size(W*D*H)mm | 540*400*700 | 640*440*890 | 750*500*1200 | 1250*500*1200 | 1250*735**1200 |
Dimensions(W*D*H)mm | 700*830*1300 | 800*870*1470 | 910*930*1785 | 1410*950*1705 | 1410*1185*1705 |
Shelf | Three floors | Three floors | Four floors | Four floors | Four floors |
Product weight | About 96kg | About 117kg | About 186kg | About 216kg | About 256kg |
-The test technical data is only applicable to the test results under the no-load condition of the equipment and the ambient temperature is 25 degrees!
-The appearance and parameters of the product are subject to change without notice. The appearance of the product may vary due to photography and printing. Please understand!
- Printer
GPRS mobile phone SMS alarm
- Computer monitoring software
- inner glass door